Explain

Explain shows, step by step, how one room's numbers were reached, in the order the engine works; it needs a run with city weather data.

Explain open beside the results

Opening it

Double-click a room row in Results and, whenever the run used a city's weather data, the right pane opens on the trace. Selecting a row — by clicking it, stepping to it with the arrow keys, or clicking the room on the drawing — does not open the pane: the double-click is the one gesture that asks for an explanation, so browsing the table never costs you the width. Once the pane is open, moving the selection to another room takes the trace with it. The header names the room, its floor and area, then reads "Peak: <month>, <hour> — <verdict>", with the verdict one of "hottest-day case governs", "most-humid-day case governs", "peak dry-bulb method (single case)", or "fixed month and hour (no search)".

Close Panel, at the foot of the pane, shuts the right pane altogether and gives its width back to the results table.

The graph

Two mini-charts show the month×hour search behind the peak: twelve month bars, the winning month highlighted, and below it that month's 24-hour profile with the peak hour marked. Hover a bar for its exact value. The profile is the total load, and the envelope alone is drawn as a thinner line beneath it, so the gap between the two is what people, lights, equipment, fresh air and infiltration add at each hour (and, for a room that follows a schedule, the schedule's effect).

The Explain panel

Rooms with no exterior wall or roof, no fresh air and no infiltration show "No envelope exposure — load is internal gains and ventilation only." in place of the graph; an interior room with people or fresh air is searched like any other, because its fresh air follows the design day. A conditions line above the graph also reports how much of the year was searched: "All 12 months × 24 hours evaluated; worst = <month>, <hour> (see graph).", or, when the load configuration fixes a specific month and hour, "Fixed at <month> <hour> (Load config); that month's 24 hours shown (see graph)." See How the worst hour is found for the search itself.

The steps

Three groups — four when the configuration calculates heating loads — list the cards behind the totals, each in the order the engine works. When the room follows a schedule, the People, Lighting, Equipment and Ventilation cards each list the Schedule factor they used at the winning hour; the fresh-air cards show it twice, once for the per-person part and once, always 1.00, for the per-area part.

Above the cards, one sentence says how the schedule was read: "No schedule assigned. People, lighting, equipment and outside air count at 100 % every hour." for an unscheduled room, which schedule was followed and the three percentages at the winning hour otherwise. The schedule is named in full, source first, for example ECSBC 2024 · Hospitality · Guest room, weekday; a Custom schedule made by Duplicate also names what it is based on, and where a space type has no curve of a kind, Explain adds one sentence per missing curve. For a scheduled room a closing line, "Without a schedule this room would be …", gives the figure and hour the room would have had at Always 100%.

Sensible

Wall conduction (one card per exterior orientation, noting the exterior length of a partly exterior wall and its Exterior wall type), Roof conduction, Window solar (one card per orientation), Glass conduction (one card per orientation), Partition conduction, Ground floor conduction, People — sensible, Lighting, Equipment, Ventilation — sensible, Infiltration — sensible (only for a room with an Infiltration figure) and, only with "Peak dry-bulb & wet-bulb", a closing Design case check that names the losing case in words — the hottest day or the most-humid day — and its total. See How the worst hour is found, Construction and Room properties for where each figure comes from.

With the radiant delay on (see Construction), each card that is delayed shows two formula lines: first Heat gain q(h), the card's own formula, then Cooling load, the industry-standard delay that turns that heat gain into load. The card's inputs then end with the gain at the hour, the Radiant fraction r and the Radiant time series it used.

A room ticked for LEED extra fresh air shows one more line on both Ventilation cards, LEED extra fresh air, with the project percentage; the outdoor-air flow's note then reads the minimum, the LEED share added to it, and the total used. The line appears only for rooms ticked for LEED (see LEED extra fresh air).

The partition step lists each interior wall that carries load, with its Interior wall type, U-value, the length charged and why, and a final Not charged line for walls facing air-conditioned rooms.

Latent

People — latent, Ventilation — latent and, for a room with an Infiltration figure, Infiltration — latent — the moisture-side gains left out of the Sensible group above.

Coil

Room sensible heat (RSH), Room latent heat (RLH), Effective room sensible heat (ERSH), Effective room latent heat (ERLH), Effective sensible heat factor (ESHF), Grand total heat (GTH), Apparatus dew point (ADP), Dehumidified air quantity and Supply air temperature — the same chain covered under Design margins and Coil and duct allowances.

Beneath the cards, one line reports how the coil search ended: "ADP: no solution — the ESHF line never meets the saturation curve; reheat required.", "ADP: no solution above 0 °C — the coil would frost.", or, when a coil was found but the room draws more fresh air than it can supply, "Outside air exceeds the supply air — the room would run on full outside air." With a Fixed ADP that is too warm, the line reads "ADP fixed at … by the config, but this room needs … — the room will run more humid than designed.", and the conditions block names the fixed value. A room with a Min airflow always gains a Minimum airflow card showing the calculated flow and the minimum, and a line: "Supply air set by the room's minimum airflow; the extra air bypasses the coil, so the coil and its load are unchanged (Load config)." or "Supply air set by the room's minimum airflow; reheat … added to the grand total (Load config)." when the minimum won, with Reheat and Grand total heat with reheat cards when reheat was chosen; or "Minimum airflow …; the calculated supply air … is larger, so the minimum does not apply." when it did not. A capacity line follows.

Heating

Shown only when the run's configuration has Calculate heating loads ticked. Wall heat loss, Glass heat loss, Roof heat loss, Partition heat loss, Ground floor heat loss, Fresh air and infiltration heat loss, Heating safety margin, Humidification and Heating airflow check, each on the one winter design day named in the conditions block above the graph ("Winter: … DB / … WB outdoor"). See Winter design for the settings behind them. Opening Explain from the Heating Load tab of the results scrolls straight to this group.

Room changed since last calculation

"Room changed since last calculation — this explains the current inputs. Recalculate to refresh the table." appears when re-running the room now would give a different total than the row on screen. Two other placeholders can appear in place of the trace: "Recalculate to explain this row.", shown when the room or floor no longer matches the last calculation, and the same message Calculate shows when the configuration has no climate data, followed by "Then recalculate."